L_PAGE_HLAVNI_NAVIGACE


Switch modules

GM-R20 – Switch module – 2 channels

GM-R20 is a power circuit’s control switch module. It allows for switching of 2 independent channels including monitoring the existence of input phase for each of the two channels. The module gets connected to a GR-U01 unit system bus. Switched state of the relay and existence of the phase are indicated by LED.

 

 

 

Specification:

Power supply voltage: 5/24V DC from system bus
Output relay contacts: 250V/16A AC, NO
Phase monitoring: max. 250V AC
Work temperature: -10°C to + 50°C
Casing: IP20
Installation: to DIN bar, 2M


2x NO relay switch contact
2x input for phase existence monitoring
5x indicative LED
Connection to system bus using connectors.

GM-R120 - Switch module – 12 channels

Relay module for power lighting circuits control. It allows for independent 12-channel switching. The module is connected to system bus of GR-U01. Relay switch state is indicated by red LED diods.

 

 

Specification:

Power supply voltage: 5/24V DC from system bus
Output relay contacts: 250V/10A AC, NO
Phase monitoring: max. 250V AC
Work temperature: -10°C to +50°C
Casing: IP20
Installation: to DIN bar, 8M

12x relay (NO) switch contact
12x LED for switch state indication
Connection to system bus via connectors
Intended for lighting circuits mainly

GM-R21 – Switch module

Relay module for control of power circuits. It provides for the stairway switch function (order 6) in case of linking the links (FCE A) or can be used as double switchcontact. The module is connected to system bus of GR-U01. Relay switch state is indicated by color LED’s.

 

 

 

Specification:

Power supply voltage: 5/24V DC from system bus
Output relay contacts: 250V/16A AC, NO
Phase monitoring: max. 250V AC
Work temperature: -10°C to +50°C
Casing: IP20
Installation: to DIN bar, 2M

2x switch relay contact
5x indicative LED
Connection to system bus using connectors

GM-Z10 – Window blinds control module

Relay module for window blinds/curtain motion control – 1 channel. Doubled contacts of input terminal make connection of 2 motors with same function possible. Warning: only motors that allow parallel connection can be parallelly connected! Module is connected to system bus of GR-U01. Controlled window blinds status and phase existence on input are indicated by color LED’s

 

 

Specification:

Power supply voltage: 5/24V DC from system bus
Window blinds motor supply input: 1x 250V AC max. 5A
Output relay contacts: 250V/5A AC: max. 250V AC
Work temperature: -10°C to 50°C
Casing: IP20
Installation: to DIN bar, 2M

2x relay contact switch
1x input for phase existence monitoring
5x indicative LED
Connection to system bus using connectors
Blinking LED show window blind direction up

GM-Z60 - Window blind control module

GM-Z60Relay module for window blinds/curtain motion control – 6 channels. It is possible to connect up 6 independent motors to the unit, each can be controlled separately. Module is connected to system bus of GR-U01 unit. It is not possible to monitor existence of phase with this module. Controlled window blinds status is indicated by color LED’s.

 

 

Specification:

Power supply voltage: 5/24V DC from system bus
Window blinds motor supply input: 6x 250V AC
Output relay contacts: 250V/5A AC
Phase monitoring: max. 250V AC
Work temperature: -10°C to + 50°C
Casing: IP20
Installation: DIN bar, 8M

6 x relay switch contact
19x indicative LED of relay
Connection to system bus using connectors

GM-IO2 – Current measuring module

This is a module for monitoring power circuits. The unit contains two independent channels, on both of which input phase existence can be monitored and instant flowing current is measurable. Module is connected to system bus of GR-U01. The status of the unit is indicated by color LED`s. Possible ways of implementing this module are measuring of plugged devices` energy consumption thus figuring their operating costs or interdependent blocking of devices causing ruling out of exceeding main wiring limits.

 

Specification:

Power supply voltage: 5/24V DC from system bus
Throughput switch: 250V/16A AC for each channel
Measurement range: 0 – 16 A
Work temperature: -10°C to +50°C
Casing: IP20
Installation: to DIN bar, 2M

2x Throughput channel for measuring
5x indicative LED
Connection to system bus using connectors

GM-AD01 - 0 ÷ 10 V controlling module

Module allowing connection with other systems, which allow for control using standardized signals 0 - 10 V, such as heating, A/C, solar systems. The unit contains one input channel and one output one. The output channel can be used also for dimmer controls or lighting devices with semiconductor ballast. Module is connected to system bus of GR-U01. The status of the unit is indicated by color LED`s.

 

 

Specification:

Power supply voltage: 5/24V DC from system bus
Output: 0 ÷10 V/ 20 mA
Input: 0 ÷ 10 V
Work temperature: -10°C to + 50°C
Casing: IP20
Installation: to DIN bar, 2M

1x output channel
1x input channel
2x indicative LED
Connection to system bus using connectors

GM-DA04 - 0 ÷ 10 V output module

This module is equipped with 4 independent outputs of 0 - 10 V signals. Primary usage of the module is to control dimmers, lighting devices with semiconductor ballast or MT010-type proportional thermoheaders. For those, an auxiliary power source GX-POW24 is required. Module is connected to system bus of GR-U01. The status of the unit is indicated by color LED`s.

 

 

Specification:

Power supply voltage: 5/24V DC from system bus
Output: 0 ÷10 V/ 20 am
Work temperature: -10°C to + 50°C
Casing: IP20
Installation: to DIN bar, 2M

4x output channel
5x indicative LED
Connection to system bus using connectors

GM-H60 – Thermoheader control module

Module for regulatory devices within heating systems, using electric valves mounted on radiators. The unit is equipped with 6 outputs for direct connection of two-state thermoheaders MT4. On the outputs, voltage from internal power source is switched. Module is connected to system bus of GR-U01. The status of the unit is indicated by color LED`s.

 

Specification:


Power supply voltage: 24V DC
Fuse: electronic in power source
Output: 24 V DC/ max. 2 A for each channel
Work temperature: -10°C to + 50°C
Casing: IP20
Installation: to DIN bar, 8M

6x output channel
12x indicative LED
Connection to system bus using connectors

GILD system features

  • The complex system
  • Independent of actual control items design
  • Usable in both newly built and reconstructed buildings
  • Easy installation and configuration
  • All housing functions under central management
  • High rate of return due to energy savings
  • Original Czech product

Pressentation of GILD system

↑ up